Standard code |
|
DXA1240 (Excellence / Premium)
DXA1712 (Evolution)
DXA1705 (Reference) |
DXA1247 (Excellence / Premium)
DXA1711 (Evolution)
DXA1706 (Reference) |
Maximum airflow |
m3/h |
230 |
Other nominal airflows |
m3/h |
80 / 140 / 200 / 230 |
Airflow compensation (filter clogging) |
|
Automatic |
Airflow balance (supply and exhaust) |
|
Automatic |
Acoustics |
|
|
|
Sound power level Lw @ 161 m3/h, 50 Pa |
dB(A) |
52 |
Sound power level Lwa [ a / b / c / d ] |
dB |
49 / 54 / 59 / 60 |
Ecodesign |
|
|
|
SEC, Climate for Evolution, Premium, Excellence |
kWh/(m².an) |
Cold : -84.32 / Average : -44.62 / Warm : -18.53 |
SEC, Climate for Reference |
kWh/(m².an) |
Cold : -78.75 / Average : -39.31 / Warm : -14.09 |
Label (EU Ecodesign Directive) |
|
A+ (for excellence, Premium, Evolution) – A (for Reference) |
Ecodesign Information |
|
Download the Ecodesign Information |
Download the Ecodesign Information |
ErP Label |
|
Download the ErP DXA1240GM Label
Download the ErP DXA1240EX Label |
Download the ErP DXA1247GM Label
Download the ErP DXA1247EX Label |
Electrics |
|
|
|
Power supply |
|
230 VAC, 50 Hz |
Motor type |
|
EC (x2) |
Power consumption @ 161 m3/h @50 Pa |
W |
36.5 |
Power consumption @ 230 m3/h @50 Pa |
W |
92.0 |
Sensors connections |
|
RJ12 |
Demand control |
|
|
|
Compatible versions of DX System |
|
Excellence / Premium / Evolution / Reference |
Min – Max number of sensors for modulation at supply |
|
1 – 5 for Excellence – At least 1 for Premium – None for others |
Min – Max number of sensors for modulation at exhaust |
|
1 – 5 for Excellence / Premium |
Sensors type at supply |
|
Presence / CO2 (Excellence / Premium) |
Exhaust units type |
|
Humidity / presence / switch / CO2 / VOC (Excellence / Premium / Evolution) |
Characteristics |
|
|
|
Exchanger |
|
Polystyrene / Counter flow type / 93 % efficiency |
Filters |
|
On supply air: 2 x F7 / On exhaust air: 1 x G4 |
Weight |
kg |
23 |
Colour |
|
Black / grey EPP -white painted Galvanized steel houssing (option) |
Material (main) |
|
Expanded polypropylene (EPP) covered by a white galvanized metal sheet (optionnal) |
Dimensions (H x W x L) |
mm |
with duct connectors: 1 428 x 552 x 545 without duct connectors: 1 188 x 552 x 545 |
Certifications |
|
CE |
Installation |
|
|
|
Max. number of main rooms |
|
6 |
Max. number of technical rooms |
|
5 |
Connections |
|
2 x (2 x ø160 mm) |
Installation |
|
2 wall fixed rails |
Other functions (in option) |
|
|
|
Interface |
|
2.8″ Colour Touch Screen interface (Excellence / Premium) Control module / Wifi (Evolution / Reference) |
Bypass |
|
Controlled by outdoor temperature / Also used for free cooling |
Pre-heating (optional) |
|
With resistance in fresh air ductwork from outside |
Condensation management |
|
Condensate pump |
Exhaust through siphon |
Temperature of use |
|
|
|
Installation room |
|
Frost Free: +5°c < T° < +50°C |
Incoming outdoor fresh air or Extract |
|
-5°c < T° < +50°C without pre-heating -26°c < T° < +50°C with pre-heating |