Standard code |
|
DXR1225 (Excellence / Premium) DXR 1714 (Evolution) DXR1708 (Reference) |
Airflow characteristics |
|
|
Maximum airflow |
m3/h |
230 |
Other nominal airflows |
m3/h |
80 / 140 / 200 /230 |
Airflow compensation (filter clogging) |
|
automatic |
Airflow balance (supply and exhaust) |
|
automatic |
Acoustics |
|
|
Sound power level Lw @ 161 m3/h, 50 Pa |
dB(A) |
40 |
Certifications |
|
CE, EAC |
Electrics |
|
|
Power supply |
|
230 VAC, 50 Hz |
Motor type |
|
EC (x2) |
Power @ 161 m3/h @50 Pa |
W |
34.2 |
Power @ 230 m3/h @50 Pa |
W |
91.0 |
Sensors connections |
|
RJ12 / RJ45 |
Demand control |
|
|
Compatible versions of DX System |
|
Excellence / Premium / Evolution / Reference |
Min – Max number of sensors for modulation at supply |
|
1 – 5 for Excellence / Premium |
Min – Max number of sensors for modulation at exhaust |
|
1 – 5 for Excellence / Premium |
Sensors type at supply |
|
Presence / CO2 |
Exhaust units type |
|
Humidity / presence / switch / CO2 / VOC |
Characteristics |
|
|
Exchanger |
|
Aluminium / Counter flow type / 82 % efficiency |
Filters |
|
On supply air: 1 x F7 / On exhaust air: 1 x G4 |
Weight |
kg |
46 |
Colour |
|
White for Excellence / Premium – galvanized steel for Evolution / Reference |
Material (main) |
|
Galvanised steel with phonic and thermal insulation |
Dimensions (H x W x L) |
mm |
With duct connectors: 260 x 650 x 1 200 Without duct connectors: 260 x 650 x 1 160 |
Ecodesign |
|
|
SEC, Climate for Evolution, Premium, Excellence |
kWh/(m².an) |
Cold : -80.65 / Average : -42.38 / Warm : -17.83 |
SEC, Climate for Reference |
kWh/(m².an) |
Cold : -73.27 / Average : -36.74 / Warm : -13.18 |
Label (EU Ecodesign Directive) |
|
A+ (for Excellence / Premium / Evolution) – A (for Reference) |
Ecodesign Information |
|
Download the Ecodesign information |
Ecodesign label |
|
Download the ErP label DXR1225GM
Download the ErP label DXR1225EX
Download the ErP label DXR1093GM |
Installation |
|
|
Max. number of main rooms |
|
6 |
Max. number of technical rooms |
|
5 |
Connections |
|
2 x (2 x ø160 mm) |
Installation |
|
Horizontal only, to the false ceiling / 4 points of attachment |
Other functions |
|
|
Interface |
|
2.8″ Colour Touch Screen interface (Excellence / Premium) Control module / Wifi (Evolution / Reference) |
Bypass |
|
Controlled by outdoor temperature / also used for free cooling |
Preheating (optional) |
|
With resistance in fresh air ductwork from outside |
Condensation management |
|
Exhaust through lateral tube / optional condensate pump |
Temperature of use |
|
|
Installation room |
|
Frost Free: +5°c < T° < +50°C |
Incoming outdoor fresh air or Extract |
|
-5°c < T° < +50°C without preheating -26°c < T° < +50°C with preheating |